فاکتور های موثر در تعیین سایز کابلهای فشار متوسط
Allowable voltage-drop for normal operating load.
o Allowable voltage-drop for future operating load as determined by motor's Service Factor.
o Allowable voltage-drop for starting condition.
o Allowable voltage-drop for motors to be re-accelerated following a voltage interruption.
o Type of starting, i.e., full-voltage, reduced-voltage, part-winding, delta-wye, VFD, etc.
o Short-circuit withstand capability for an in-close fault (eg, motor starter.)
o Ground or earth-fault capability for a far-end fault (eg, motor terminal.)
o Plastic or rubber sheath resistance to chemical attack.
o Metallic screen or shield material withstand capability for excessive heating.
o Derating factor(s) covering installation, i.e., free-air, direct-burial (dry, wet) in conduit (duct bank, steel, plastic.)
o Derating factor(s) covering conductor material (Cu, Al.)
o Derating factor(s) covering construction, round or sector shaped, 3x1/c, 1x3/c, 3-1/2 or 4-core, overall sheath and/or shield.
o Derating factor(s) covering insulation type and voltage level
o Derating factor(s) covering termination type (bolt, lug, clamp, brazed, soldered.)
o If direct-burial, then consider the possibilit of subsidence